SMA “Riso”

PV generator insulation

Error code
Riso
Category
PV generator insulation
Manufacturer
SMA
Models
Sunny Boy (SB)

1What the error means

The insulation resistance of the PV generator to earth is below the limit. The inverter does not start until the insulation is restored — it indicates a ground fault on the DC side.

2Possible causes

  • Moisture in junction boxes, connectors or modules
  • Damaged DC cables
  • Faulty module

3What to do

  1. Note whether it appears after rain or early in the morning, when there is moisture.
  2. Measure the insulation resistance of each string.
  3. If the PV generator is fine, check the inverter's measuring circuit.