SMA Error 6801

Input A defective

Error code
6801
Category
Input A defective
Manufacturer
SMA
Models
Sunny Tripower (STP)

1What the error means

Self-diagnosis: the inverter detected a problem on DC input A, i.e. the first MPP tracker. The cause may be the string connected there or the input circuit itself.

2Possible causes

  • Fault in the string on input A — voltage, polarity or short circuit
  • Fault in the inverter's MPP tracker A

3What to do

  1. Measure the voltage and polarity of the string on input A.
  2. Try the same string on input B: if the fault moves, the PV generator is at fault; if it stays on A, the inverter is at fault.

Same code group

Code 6801 belongs to the same group as 6802 — they share the same cause and the same remedy.