SMA Error 901

Earthing

Error code
901
Category
Earthing
Manufacturer
SMA
Models
Sunny Tripower (STP)

1What the error means

The inverter detected that the protective earth (PE) conductor is missing or not correctly connected. Without proper earthing it is not allowed to operate.

2Possible causes

  • Disconnected or loose earth conductor
  • Oxidised earth contact
  • Wiring error

3What to do

  1. Check the PE conductor at the inverter and in the distribution board.
  2. Measure the earth continuity.
  3. If the earthing is correct and the fault remains, check the inverter's measuring circuit.