- Error code
- OS 79
- Category
- Insulation resistance
- Manufacturer
- KACO
1What the error means
The insulation resistance of the PV generator is being measured. The inverter runs the check before connecting — a normal stage.
On the display or in the monitoring software it appears as OS 79.
2Possible causes
- Moisture in junction boxes, connectors or modules
- Damaged or worn DC cables
- Faulty module
3What to do
- Note whether it appears after rain or early in the morning.
- Measure the insulation resistance of each string to earth.
- Check connectors and junction boxes for moisture.
- If the PV generator is fine, check the inverter's measuring circuit.