- Error code
- FS 41 – FS 46
- Category
- Phase failure
- Manufacturer
- KACO
1What the error means
Grid feed-in is not possible. The display shows which phase has the problem — codes FS 41 to FS 46 correspond to the phases and the limits that were violated.
On the display or in the monitoring software it appears as FS 41 – FS 46.
2Possible causes
- One phase missing or interrupted
- Tripped fuse on one phase
- Unbalanced grid
3What to do
- Measure all three phases at the inverter.
- Check the fuses on each phase.
- If all three phases are normal, check the measuring circuit.
Codes covered
This fault appears with the codes FS 41 – FS 46. The manufacturer documents them as a single fault — the number indicates the stage or the phase in which it was detected.