Kostal Piko — “xxx” display

The inverter does not start

Error code
xxx
Category
The inverter does not start
Manufacturer
KOSTAL
Models
PIKO 3.0 – 10.1 (the whole first generation)

1What the error means

The Kostal Piko display shows no error code, only “xxx”. The inverter has normal voltage from both the grid and the panels, yet it stays in the off position and never goes into production — as if it never completes its start-up.

It is one of the most common faults of the first Piko generation (3.0 to 10.1). It appears on units with many years of operation — usually at around 100,000 kWh of production — and is almost always an internal fault of the inverter, not of the installation.

2Possible causes

  • Fault on the control board, which does not complete the start-up (wake-up) sequence
  • Worn capacitors in the internal power supply of the control board
  • Communication problem between the control board and the power stage
  • More rarely: fault of the display or the display board

3Possible solution

Switch off the grid (AC) breaker and switch it back on after 2–3 minutes. In some cases the inverter starts — temporarily. If the “xxx” returns, the fault is permanent and requires repair in the lab: the control board is repaired at component level, without needing replacement of the inverter.

4What to do

  1. Make sure there is grid voltage at the inverter and that the fuses in the distribution board are OK.
  2. Switch off the grid breaker, wait 2–3 minutes and switch it back on — once.
  3. If the “xxx” persists or returns, do not keep restarting. Note the model from the nameplate and contact us — we repair this fault routinely.

Related Kostal faults

5Repair by Aineas

You send the inverter to our lab in Thessaloniki. We diagnose it, inform you of the fault and the cost, and the repair starts only after you approve it. Every inverter is tested under simulated operating conditions before delivery.