Kostal Error 400–401

DC overvoltage

Error code
400–401
Category
DC overvoltage
Manufacturer
KOSTAL
Models
Piko / Plenticore

1What the error means

DC overvoltage: the PV generator voltage exceeded the maximum permitted input voltage. This is a dangerous condition — the inverter stops so that its input is not destroyed.

2Possible causes

  • Too many modules in series for this model
  • Low temperature — the open-circuit voltage rises in winter
  • Incorrect string sizing

3What to do

  1. Disconnect the PV generator immediately.
  2. Check the number of modules per string against the maximum input voltage.
  3. If the inverter ran with overvoltage, its input needs to be checked for damage.

Codes covered

This fault appears with the codes 400–401. The manufacturer documents them as a single fault — the number indicates the stage or the phase in which it was detected.