ABB / FIMER E001 — Input OC

DC overcurrent

Error code
E001
Category
DC overcurrent
Manufacturer
ABB / FIMER

1What the error means

Input over-current: the current from the PV generator exceeded the maximum permitted limit of the input.

On the display or in the monitoring software it appears as Input OC.

2Possible causes

  • Incorrect string sizing — too much current
  • Short circuit on the DC side
  • Fault in the inverter's input circuit

3What to do

  1. Measure the current of each string and compare it with the inverter's limit.
  2. Check the DC cables for a short circuit.
  3. If the PV generator is fine, the input stage needs to be checked in our lab.

4Repair by Aineas

You send the inverter to our lab in Thessaloniki. We diagnose it, inform you of the fault and the cost, and the repair starts only after you approve it. Every inverter is tested under simulated operating conditions before delivery.