+30 2310 607032 · info@aineas.gr · Mon–Fri 09:00–17:00
Services The lab How it works Inverter Errors Contact thesolarportal.com thesolarlink. →

Sungrow Error 015

Grid overvoltage

Error code
015
Category
Grid overvoltage
Manufacturer
SUNGROW

1What the error means

Grid overvoltage, stage II (Grid Over-voltage): second level of overvoltage protection. Also check the cross-section of the AC cables.

2Possible causes

  • High grid voltage at the point of connection
  • Undersized or very long AC cable — the inverter raises the voltage while it feeds in
  • Several inverters on the same line
  • Wrong country setting

3What to do

  1. Measure the voltage at the point of connection while the inverter is feeding in.
  2. Check the cross-section and length of the AC cable.
  3. If the grid voltage is permanently high, notify the grid operator.
  4. If the voltage is normal and the fault persists, the inverter's measuring circuit needs to be checked.

4Repair by Aineas

You send the inverter to our lab in Thessaloniki. We diagnose it, inform you of the fault and the cost, and the repair starts only after you approve it. Every inverter is tested under simulated operating conditions before delivery.

← All SUNGROW errors