- Error code
- 014
- Category
- Grid overvoltage
- Manufacturer
- SUNGROW
1What the error means
10-minute grid overvoltage (10-minute Grid Over-voltage): the average voltage over a ten-minute period exceeded the limit. Also check that the inverter's country code is correct.
2Possible causes
- High grid voltage at the point of connection
- Undersized or very long AC cable — the inverter raises the voltage while it feeds in
- Several inverters on the same line
- Wrong country setting
3What to do
- Measure the voltage at the point of connection while the inverter is feeding in.
- Check the cross-section and length of the AC cable.
- If the grid voltage is permanently high, notify the grid operator.
- If the voltage is normal and the fault persists, the inverter's measuring circuit needs to be checked.